Emergency Lighting |
Monthly |
Quarterly |
Semi-annual |
Annual |
CODE |
NFPA 101 |
|
Testing |
|
|
|
|
7-9.3 |
A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. |
|
Annual Test |
|
|
|
|
7-9.3 |
An annual test shall be conducted on every required battery-powered emergency lighting system for not less than 11/2 hours. Equipment shall be fully operational for the duration of the test. |
|
Monthly |
Quarterly |
Semi-annual |
Annual |
CODE |
NFPA 101 |
|
|
Visual Inspection |
|
|
|
|
7-10.9.1 |
Exit signs shall be visually inspected for operation of the illumination sources at intervals not to exceed 30 days. |
|
Annual Test |
|
|
|
|
7-10.9.2 |
Exit signs connected to or provided with a battery-operated emergency illumination source, where required in 7.10.4, shall be tested and maintained in accordance with 7.9.3. |