Emergency Lighting

Monthly

Quarterly

Semi-annual

 Annual

CODE

NFPA 101

 

Testing

 

 

 

7-9.3

A functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds.

 

Annual Test

 

 

 

7-9.3

An annual test shall be conducted on every required battery-powered emergency lighting system for not less than 11/2 hours. Equipment shall be fully operational for the duration of the test. 

 

Exit Signs/Lighting

Monthly

Quarterly

Semi-annual

 Annual

CODE

NFPA 101

 

Visual Inspection

 

 

 

7-10.9.1

Exit signs shall be visually inspected for operation of the illumination sources at intervals not to exceed 30 days.

 

Annual Test

 

 

 

7-10.9.2

Exit signs connected to or provided with a battery-operated emergency illumination source, where required in 7.10.4, shall be tested and maintained in accordance with 7.9.3.