All-Saf Fire Protection offers professional service for your emergency and exit lighting in compliance with NFPA 101-31-1.3.7. This standard mandates that all emergency and exit lighting receive testing at least every 30 days with accompanying written reports of the testing results. Our staff can assist you with any aspect of routine maintenance form providing support in terms of training and parts to actually performing the services required by law. Contact our staff today to discuss your service requirements. |
|
NFPA Standard No. 101-31-1.3.7 |
"A functional test shall be conducted on every required emergency lighting system at 30-day intervals for a minimum of 30 seconds. An annual test shall be conducted for the 1 1/2 hour duration. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.” |
|
All-Saf Fire Protection, Inc. CODE Compliance Guide Exit Lighting |
|
|
| |
Testing Procedures for Emergency Lights |
- 90 Minute full function test
- Disconnect AC power supply to each emergency light
- Check battery and lens for evidence of sulfating
- Clean each emergency light and lens as required
- Adjust beam for proper alignment
- Place testing label on the emergency light and record in testing log
- Troubleshooting/repair may also include
- Check and adjust charging system voltage
- Check line voltage to remote fixtures
|
|
| |
|
| |
| |